Molded Case Circuit Breakers

Thermal-magnetic and electronic-trip circuit breakers for feeder, motor and main protection, sized by frame size, ampere trip rating and interrupting capacity. Search by voltage class and trip rating, or describe the load being protected and let ChatMRO match the right breaker.

  • 30M+ parts indexed
  • Procure in < 60 seconds
  • No credit card required

Searchable by Spec

Indexed on full specifications rather than titles alone, so a spec can be searched directly.

Backed by Raptor Supplies

The same suppliers, pricing desk and people standing behind every quote.

US & Worldwide

Serving the US, with fulfilment across the UK, EU, Singapore and Australia.

Technical Foundation

What Is a Molded Case Circuit Breaker?

A molded case circuit breaker (MCCB) is an electromechanical overcurrent protection device housed in an insulated molded plastic case, combining manual on/off switching with automatic tripping on overload or short-circuit conditions. Thermal-magnetic breakers use a bimetallic strip for time-delayed tripping on sustained overload (protecting against gradual overheating) and a magnetic element for near-instantaneous tripping on short-circuit-level fault current; electronic trip breakers replace this with a microprocessor-based trip unit offering adjustable long-time, short-time, instantaneous and ground-fault (LSIG) protection curves.

Breakers are specified by frame size (the physical case rating, e.g. 100A, 225A, 400A frame, which sets the maximum trip setting achievable in that case), trip rating (the actual continuous current the breaker is set to carry before tripping, which can be lower than the frame size), and interrupting rating (AIC, the maximum fault current the breaker can safely interrupt without failure) — the AIC rating must equal or exceed the available fault current at the point of installation, per NEC 110.9 and coordination study requirements.

Prefer a quick quote?

Get Molded Case Circuit Breakers Pricing in Your Inbox

Skip the search — tell us the frame size, trip rating and interrupting capacity (AIC) needed and we will come back with pricing.

SpecWhat It MeansWhy It Matters
Frame Sizee.g. 100A, 225A, 400A, 800A frameSets the physical case rating and the maximum trip setting the breaker can be built or field-adjusted to
Trip RatingActual set continuous current rating within the frameCan be lower than frame size — sized to the protected conductor's ampacity, not just the frame
Interrupting Rating (AIC)e.g. 22kA, 42kA, 65kA at rated voltageMust meet or exceed available fault current at the installation point — undersized AIC is a serious safety hazard
Trip Unit TypeThermal-magnetic (fixed/adjustable) vs. electronic (LSIG)Electronic trip units allow field-adjustable, more selective coordination between upstream and downstream breakers
Pole Configuration1, 2, or 3-poleMust match the circuit's phase configuration — 3-pole for three-phase feeders, 1 or 2-pole for single-phase branch circuits

Shop Molded Case Circuit Breakers

Browse Molded Case Circuit Breakers Sub-Categories

Organised by trip technology and application. Pick a sub-category, or describe the frame size and interrupting rating and let ChatMRO match the breaker.

How it works

From Half-Remembered Part Number to PO, in Three Steps.

01

Ask

Type an MPN, paste a spec sheet, or describe the part in plain English. ChatMRO understands engineer-speak.

02

Compare

Side-by-side specs, cross-references, and equivalents from multiple sources — without the clutter of endless browser tabs.

03

Quote & Buy

Request a quote or add to cart. Volume discounts, VAT-aware pricing, and consolidated procurement — all in one place.

Applications

Where Molded Case Circuit Breakers Get Used

MCCBs are specified anywhere a circuit needs adjustable, higher-current overcurrent protection beyond what a standard molded-case or miniature breaker in a residential panel provides.

Electrical Switchgear & Panelboards

Main and feeder MCCBs providing the primary overcurrent protection point in a facility's distribution panel.

Motor Control Centers

Motor circuit protectors with magnetic-only trip curves sized to allow motor inrush current without nuisance tripping.

Industrial Machine Protection

Feeder breakers sized to the specific branch circuit conductor ampacity feeding production equipment.

Data Centers & Critical Power

Electronic trip breakers with adjustable LSIG settings enabling selective coordination across multiple protection tiers.

Commercial Building Distribution

Panelboard breakers protecting lighting, HVAC and receptacle branch circuits at standard trip ratings.

Renewable Energy & Utility Interconnection

DC-rated and higher-voltage MCCBs protecting solar array combiner and inverter circuits.

FAQ

Molded Case Circuit Breakers Questions, Answered

What's the difference between frame size and trip rating on an MCCB?

Frame size is the physical case rating of the breaker — it sets the maximum current the case and internal components are built to handle, such as a 225A frame. Trip rating is the actual current setting the breaker is built or adjusted to trip at, which can be lower than the frame size — for example, a 225A-frame breaker might be set to trip at 150A to match a specific conductor's ampacity. Always confirm both when specifying a replacement, since a breaker with the right frame but wrong trip setting won't protect the circuit correctly.

Why does interrupting rating (AIC) matter so much?

The interrupting rating is the maximum fault current the breaker can safely interrupt without its contacts welding shut, the case rupturing, or other catastrophic failure. If the available fault current at the installation point (determined by a fault current study) exceeds the breaker's AIC rating, the breaker can fail to clear a fault safely — this is a serious life-safety hazard, and NEC 110.9 requires equipment interrupting rating to meet or exceed available fault current.

What's the advantage of an electronic trip unit over thermal-magnetic?

Electronic trip units use a microprocessor to independently adjust long-time (overload), short-time, instantaneous, and ground-fault trip settings (LSIG), enabling much more precise and selective coordination between upstream and downstream breakers than a fixed thermal-magnetic curve allows. This selectivity reduces nuisance tripping of upstream breakers during a downstream fault, improving system uptime — at a higher cost than a standard thermal-magnetic breaker.

Can I replace an MCCB with a different manufacturer's breaker in an existing panel?

Generally no — MCCBs are UL listed as part of a specific panelboard or switchgear assembly, and the panel manufacturer typically only lists specific breaker models (often their own) as suitable replacements for a given panel interior. Installing a non-listed breaker in a panel voids the panel's listing and can create a code violation and safety hazard, even if the physical dimensions appear to fit.

How do I size a motor circuit protector versus a standard feeder breaker?

A motor circuit protector (MCP) uses a magnetic-only (instantaneous) trip curve with no thermal element, since motor overload protection is typically handled separately by a motor overload relay or starter — this lets the MCP be set high enough to ride through motor starting inrush current (which can be 6-8x full load current) without nuisance tripping, something a standard thermal-magnetic feeder breaker sized the same way would not tolerate.